BOILER GAUGE GLASS BLOW THROUGH
GAUGE GLASS BLOW THROUGH
- SHUT THE STEAM SIDE VALVE
- SHUT THE WATER SIDE VALVE
- NOW OPEN THE DRAIN VALVE
- NOW GAUGE GLASS BECOME EMPTY.
- NOW OPEN THE STEAM SIDE VALVE ,IF STEAM COME OUT WITHOUT ANY DEFICIENCY WHICH MEANS STEAM SIDE IS CLEAR .
- NOW CLOSE THE STEAM SIDE
- OPEN THE WATER SIDE, IF WATER WILL COME OUT WITHOUT ANY DEFICIENCY WHICH MEANS WATER SIDE IS CLEAR.
- NOW CLOSE THE WATER SIDE
- AND CLOSE THE DRAIN VALVE.
- NOW OPEN THE WATER SIDE FIRST, WATER WILL RISE AND FILL UP THE GAUGE GLASS.
- NOW OPEN THE STEAM SIDE STEAM WILL COME INTO GAUGE GLASS AND SHOW THE EXTRACT LEVEL OF INSIDE BOILER WATER.
Notes
SURVIVER MAY ASK YOU OPEN WATER SIDE FIRST
(If we open steam side first gauge glass will breake because of lantern heat.)
Comments